Skip to main content
Siemens 5SY7525-6 — 1-Pole MCB (DIN Rail)

Siemens 5SY7525-6 SENTRON MCB, 25 A, B-Curve, 2-Pole, 15/25

MPN5SY7525-6
Active

Siemens SENTRON 5SY7525-6 miniature circuit breaker, 2-pole (1P+N), B-curve, 25 A rated, 15 kA (EN 60898) / 25 kA (IEC 60947-2), IP20, 36 mm wide.

$17.78Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7525-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityMechanical engineering / industry
5SY7525-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)15 kA
Energy limitation class3
Overvoltage categoryIII
5SY7525-6 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7525-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

What the ratings mean for your panel

The Siemens 5SY7525-6 is a 2-pole (1P+N) SENTRON miniature circuit breaker with a B-curve tripping characteristic, rated 25 A at 50/60 Hz. The B-curve means it trips between 3 and 5 times rated current — designed for resistive and lighting loads where inrush is low, not for motor starting or transformer primaries. The 15 kA breaking capacity per EN 60898 covers most commercial and light industrial panelboards; the 25 kA rating per IEC 60947-2 gives headroom for higher-fault installations where the upstream transformer is close. The 25 A rating is the continuous current at 35 °C ambient. At 40 °C it derates to 23.48 A, at 50 °C to 21.85 A, and at 60 °C to 20.1 A. The 36 mm width (2 modular units) snaps onto a DIN rail; depth is 76 mm, height 90 mm. Mounting position is any. IP20 with connected conductors means it's protected against finger contact but not moisture — suitable for dry indoor panels only, not washdown or outdoor locations. Overvoltage category III and pollution degree 3 confirm it's rated for fixed installation in industrial environments where transients are common.

Panel integration and compliance

The breaker mounts on a DIN rail via the quick assembly system — no tools needed for installation or removal. The combined terminal top and bottom accept copper conductors; the sealable feature allows locking in the OFF position for lockout/tagout procedures. Halogen-free and silicon-free construction matters for clean-room or sensitive electronic environments where outgassing could cause contact corrosion. Compliance documentation covers IEC 60898 and IEC 60947-2 as cited; the product designation follows IEC 81346-2 and DIN EN 61346-2 letter code F (protective device). Touch protection is built into the design — no additional finger-safe shrouds needed for standard panel wiring.

Frequently asked questions

Will the 5SY7525-6 drop into a panel specified for the 5SY7210-7CC?

Both are 2-module (36 mm wide) SENTRON MCBs on the same DIN-rail footprint, so mechanical fit is the same. The difference is in the rating: the 5SY7525-6 is a 25 A B-curve; the 5SY7210-7CC is a different ampacity and curve. Verify the branch circuit requirements before swapping.

MPN
5SY7525-6