Skip to main content
Siemens 5SY7602-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY7602-8 SENTRON MCB, 4P D-curve 2 A, 15/50 kA

MPN5SY7602-8
Active

Siemens SENTRON 5SY7602-8, 4-pole (3P+N) miniature circuit breaker, D tripping characteristic, 2 A rated current, 15 kA (EN 60898) / 50 kA (IEC 60947-2) breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7602-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY7602-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC2 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY7602-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089815 kA
Rated breaking capacity, per IEC 60947-250 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY7602-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY7602-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Siemens 5SY7602-8 — 4-pole D-curve MCB for industrial branch circuits

The Siemens 5SY7602-8 is a 4-pole (3P+N) miniature circuit breaker from the SENTRON series, sized at 4 modular width units (72 mm) for DIN-rail panels. Rated 2 A at 35 °C, it derates to 1.7 A at 60 °C, so the actual continuous load must be checked against the panel ambient temperature. The DC rating of 15 kA per IEC 60947-2 covers DC branch circuits, common in control power or battery-backed loads.

Integration — panel fit and wiring

The breaker is sealable for tamper-proof applications. Halogen-free and silicon-free construction avoids corrosive off-gassing in sealed enclosures or near sensitive contacts. Ambient humidity limits: max 95% at 55 °C, derating to 35% at 75 °C.

Frequently asked questions

Where can I buy 5SY7602-8?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SY7602-8?

15 kA per EN 60898 for general distribution, 50 kA per IEC 60947-2 for industrial duty, and 15 kA at DC per IEC 60947-2.

What does the D tripping characteristic mean?

The D curve trips at 10–20 times the rated current (2 A), so it handles high inrush from small motors, transformers, or solenoid banks without nuisance tripping.

What is the temperature derating for 5SY7602-8?

Rated 2 A at 35 °C, derated to 1.85 A at 45 °C, 1.8 A at 50 °C, 1.75 A at 55 °C, and 1.7 A at 60 °C. Ambient temperature inside the enclosure governs the actual continuous load.

MPN