Skip to main content
Siemens 5SY7616-6 — 4-Pole MCB (DIN Rail)

Siemens SENTRON 5SY7616-6 MCB, 4P B-Curve, 15/25 kA

MPN5SY7616-6
Active

Siemens SENTRON miniature circuit breaker, 5SY7616-6, 4-pole (3P+N), B-curve, 15 kA per EN 60898 / 25 kA per IEC 60947-2, 400 V AC, 72 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7616-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY7616-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SY7616-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY7616-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY7616-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY7616-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.8 W

Product details

Siemens SENTRON 5SY7616-6 — B-curve 4-pole MCB

The Siemens SENTRON 5SY7616-6 is a 4-pole (3P+N) miniature circuit breaker with a B-curve tripping characteristic, designed for 400 V AC systems at 50/60 Hz. Its 15 kA rated breaking capacity per EN 60898 and 25 kA per IEC 60947-2 give it headroom for high-fault installations — the IEC 60947-2 figure governs industrial panel coordination, while the EN 60898 value applies to residential or commercial final circuits. The neutral pole is switched (3P+N), so you get full isolation on all four conductors without a separate switch.

With 25 kA at 400 V AC per IEC 60947-2, this breaker coordinates cleanly upstream of downstream MCBs rated up to 15 kA — the energy-limiting class 3 keeps let-through low enough to protect branch circuits without cascading failure.

Mounting position is any, so vertical or horizontal rail orientation is fine.

Halogen-free and silicon-free construction reduces toxic smoke and silicone contamination in sensitive environments like food processing or electronics assembly. Degree of pollution 3 means it tolerates conductive dust and humidity typical of industrial floors. Sealable for lockout/tagout compliance.

Frequently asked questions

Where can I buy 5SY7616-6 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here.

What is 5SY7616-6's listed depth?

The depth is 76 mm, with an installation depth of 70 mm.

What compliance documentation does Siemens provide for 5SY7616-6?

The breaker is certified to IEC / EN 60898-1 and IEC / EN 60947-2 / UL1077. It is halogen-free and silicon-free. Compliance documentation including RoHS and REACH declarations is available from Siemens upon request.

Will 5SY7616-6 drop into a panel specified around 5SY4304-7CV?

No — the 5SY4304-7CV is a different pole count and curve. The 5SY7616-6 is a 4-pole B-curve (3P+N) in a 72 mm (4 MW) housing, while the 5SY4304-7CV is a single-pole unit. They are not footprint-compatible without rewiring the distribution board.

MPN
5SY7616-6