Skip to main content
Siemens 5SY8113-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY8113-7 SENTRON MCB, C-Curve, 1P, 30 kA IEC

MPN5SY8113-7
Active

Siemens SENTRON 5SY8113-7, 1-pole miniature circuit breaker, C-curve, 30 kA interrupting capacity at 400 V AC per IEC 60947-2, 18 mm wide, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY8113-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY8113-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY8113-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8113-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Rated 30 kA at 400 V AC per IEC 60947-2, and 15 kA at 60 V DC per the same standard. For UL 1077 applications, the interrupting rating is 5 kA. The 18 mm wide module snaps onto standard DIN rail — one modular unit, any mounting position.

At 60 V DC it still holds 15 kA, which covers most DC auxiliary bus applications in industrial control panels. The 5 kA UL 1077 rating means this is a supplementary protector in North American code — not a branch-circuit rated breaker under UL 489, so plan your SCCR coordination accordingly.

Installs in any orientation — the mounting position is unrestricted. Depth is 76 mm total; installed depth is 70 mm, which clears most standard 80 mm deep enclosures. The 18 mm width occupies one 18 mm modular unit on DIN rail. Halogen-free and silicon-free construction — important for sensitive environments like semiconductor fabs or food processing areas where outgassing contamination matters.

Holds dual certification: IEC/EN 60947-2 (the main global standard for low-voltage switchgear) and UL 1077 (supplementary protector for North America). Vibration resistance tested per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz. The terminal design accepts top and bottom combined feed — no special busbar orientation required. Sealable cover is standard, which allows lockout/tagout compliance on the panel.

Frequently asked questions

Where can I buy 5SY8113-7 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price listed here, but a quote request will return a firm number and lead time.

What is the closest functional alternative to 5SY8113-7?

The 5SY7206-7CC is the closest functional peer in the SENTRON family — same 1-pole, C-curve, 18 mm wide footprint. Check the interrupting rating and voltage on that order code to confirm it matches your required SCCR. The 5SY4101-7CV (B-curve) and 5SY4116-7CV (C-curve, different current rating) are also in the series but differ in trip characteristic or amp rating.

What compliance documentation does Siemens provide for 5SY8113-7?

The breaker carries IEC/EN 60947-2 and UL 1077 certifications. Halogen-free and silicon-free construction is declared. Vibration resistance tested per IEC 60068-2-6. Standard documentation includes the declaration of conformity, UL file listing, and RoHS/REACH compliance statements available through Siemens Industry Online Support.

Will 5SY8113-7 drop into a panel specified for 5SY7206-7CC?

Yes — same 18 mm width, same DIN rail mount, same 1-pole form factor. If the 5SY7206-7CC was specified, the 5SY8113-7 will physically fit in the same panel position without rewiring, provided the interrupting rating and amp rating match your design requirements.

MPN
5SY8113-7