Skip to main content
Siemens 5SY8113-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY8113-8 SENTRON MCB, D Curve, 1P, 30 kA IEC

MPN5SY8113-8
Active

Siemens SENTRON 5SY8113-8, miniature circuit breaker, D characteristic, 1-pole, 30 kA per IEC 60947-2, 5 kA per UL 1077, 400 V AC, 60 V DC, 18 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8113-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY8113-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY8113-8 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8113-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY8113-8 — D-Curve MCB for Industrial Circuits

It is rated for 400 V AC (440 V AC single- or multi-phase) and 60 V DC (72 V DC maximum).

The D curve (tripping characteristic class D) means this breaker tolerates inrush currents up to 10–20 times rated current for short durations — exactly what motor starters, transformers, and inductive loads draw on startup. D is deliberately slower on small overcurrents to avoid nuisance trips on high-inrush equipment. The 30 kA breaking capacity at 400 V AC (per IEC 60947-2) tells you this MCB can safely interrupt a fault current up to 30,000 A without welding its contacts or rupturing. That rating is tested under the standard's conditions — it is the maximum fault the breaker can clear and still be reusable after inspection. The UL 1077 supplementary-protector rating of 5 kA is a separate, lower standard for North American panels where the breaker is not the primary service disconnect.

Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz. The breaker carries IEC/EN 60947-2 and UL 1077 approvals; compliance documentation (RoHS, REACH) is provided by Siemens for the SENTRON series.

Frequently asked questions

How do I get current pricing and availability for 5SY8113-8?

The 5SY8113-8 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SY8113-8's listed depth (76 mm) on this component line?

The 5SY8113-8 has a depth of 76 mm, with an installation depth of 70 mm.

What is 5SY8113-8's listed width (18 mm) on this component line?

The 5SY8113-8 has a width of 18 mm, which is one modular unit on standard DIN rail.

What compliance documentation does Siemens provide for 5SY8113-8?

The 5SY8113-8 is certified to IEC/EN 60947-2 and UL 1077. Siemens provides RoHS and REACH compliance documentation for the SENTRON series; the breaker is halogen-free and silicon-free.

MPN
5SY8113-8