Siemens 5SY8115-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY8115-7 SENTRON MCB, 1.6 A C-Curve, 1P, 70 kA

MPN5SY8115-7
Active

Siemens SENTRON 5SY8115-7 miniature circuit breaker, 1-pole, C characteristic, 1.6 A rated current, 70 kA breaking capacity per IEC 60947-2, 440 V AC, 72 V DC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8115-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY8115-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY8115-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8115-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY8115-7 is a 1-pole SENTRON miniature circuit breaker with a C tripping characteristic, rated 1.6 A at 440 V AC (single- or multi-phase) and 72 V DC. On the DC side, it's rated 15 kA per the same standard, so it handles DC control circuits up to 72 V.

Rated current holds at 1.6 A up to 45 °C. At 50 °C it derates to 1.56 A, at 55 °C to 1.52 A. The breaker operates from -40 °C to 75 °C ambient, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% up to 75 °C.

Depth is 76 mm (70 mm installation depth), height 90 mm, width 18 mm (1 modular unit). Sealable, halogen-free, silicon-free — relevant for environments sensitive to outgassing or where tamper evidence is required.

Frequently asked questions

Where can I buy 5SY8115-7 and how do I get a price?

The 5SY8115-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings for 5SY8115-7?

Rated 1.6 A at 440 V AC (single- or multi-phase) and 72 V DC, C tripping characteristic, 1-pole, 70 kA breaking capacity per IEC 60947-2 at 440 V AC, 15 kA at 72 V DC. Width 18 mm (1 modular unit), depth 76 mm, height 90 mm.

What compliance documentation does Siemens provide for 5SY8115-7?

The 5SY8115-7 is designed to IEC 60947-2 and EN 60898 standards. It carries IP20 protection with connected conductors, pollution degree 3, overvoltage category III, and is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations are available from Siemens documentation for this SENTRON series.

MPN