It snaps onto DIN rail in one modular width unit (18 mm), so it fits tight panel layouts without crowding adjacent breakers.
Rated 16 A at AC, but that figure holds only up to 45 °C ambient. At 50 °C it derates to 15.5 A, and at 55 °C to 14.99 A (–). The 30 kA breaking capacity at 400 V AC (IEC 60947-2) is the figure that governs fault clearance in industrial distribution; the 5 kA rating under UL 1077 and CSA C22.2 No. 235 is the supplementary-protector limit for North American panels. For DC circuits, it breaks 15 kA per the same IEC standard. The housing is IP20 with conductors connected, so it needs an enclosure for washdown or outdoor use; it is not a standalone weatherproof device.
The breaker carries IEC 60947-2, UL 1077, and CSA C22.2 No. 235 approvals. Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz. The product is sealable — a lockable cover can be fitted to prevent unauthorized reset.