Skip to main content
Siemens 5SY8205-8 — 2-Pole MCB (DIN Rail)

Siemens 5SY8205-8 SENTRON MCB, 2P D 0.5A, 70kA

MPN5SY8205-8
Active

Siemens SENTRON 5SY8 series, miniature circuit breaker (MCB), 2-pole, D tripping characteristic, 0.5 A rated current, 70 kA breaking capacity at 400 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8205-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY8205-8 — Electrical
ParameterValue
Number of poles2
5SY8205-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY8205-8 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY8205-8 — Environmental
ParameterValue
Pollution degree3

Product details

What the 70 kA SCCR means for your panel

The Siemens 5SY8205-8 is a 2-pole SENTRON miniature circuit breaker with a D tripping characteristic, rated 0.5 A at 400 V AC. The D-curve (10–20× In magnetic trip) is deliberate: it rides out the inrush of a small transformer, solenoid bank, or motor starter without nuisance tripping, then clears fast on a hard fault.

Thermal derating and environmental range

The 0.5 A rating is at 45 °C ambient. At 50 °C it derates to 0.48 A, and at 55 °C to 0.47 A — a linear drop of about 4% per 5 °C step. The operating range spans -40 °C to 75 °C, with humidity limits of 95% at 55 °C, tapering to 35% at 75 °C. That wide thermal envelope suits unheated enclosures or outdoor cabinets in temperate to hot climates.

Snap-on quick assembly system, mountable in any position. Touch protection is built in, so no additional finger-safe shrouds needed for the front panel.

DC and UL ratings

For DC circuits per IEC 60947-2, the breaking capacity is 15 kA. Under UL 1077 and CSA C22.2 No. 235 (supplementary protector recognition), it is rated 5 kA at 400 V AC. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. These ratings confirm it for industrial machinery panels that see moderate vibration from nearby drives or conveyors.

Frequently asked questions

What does the D-curve mean on this 0.5 A breaker?

The D tripping characteristic (magnetic trip at 10–20× In) means it tolerates the high inrush of small transformers, solenoid valves, or motor starters without nuisance tripping, while still clearing a hard short fast. For a 0.5 A rating, that inrush tolerance is useful on control transformers or relay coils.

What is the breaking capacity of the 5SY8205-8?

70 kA at 400 V AC per IEC 60947-2. For DC circuits it is 15 kA, and under UL 1077 / CSA C22.2 No. 235 it is 5 kA at 400 V AC.

Where can I buy the 5SY8205-8?

This part is sourced to order through our independent distribution channel. Availability and current pricing are confirmed at quote time against an RFQ — no stock or price figures are published here.

Does the 5SY8205-8 have UL or CSA approval?

It carries a UL 1077 and CSA C22.2 No. 235 supplementary protector rating at 5 kA / 400 V AC. The primary IEC 60947-2 rating is 70 kA at 400 V AC.

MPN