The Siemens 5SY8208-8 is a 2-pole miniature circuit breaker from the SENTRON 5SY8 series, with a D tripping characteristic and an 8 A rated current at 400 V AC. It's also rated 15 kA at DC per IEC 60947-2 for up to 72 V DC, and carries a 5 kA interrupting rating under UL 1077 and CSA C22.2 No. 235 — so it's accepted in North American control-panel applications where UL 508A compliance is required, not just IEC markets. The silicon-free and halogen-free construction makes it suitable for clean-room or sensitive electronics environments where outgassing contaminants are a concern.
Mounting and wiring in the panel
Terminal clamps accept solid or stranded copper from 0.75 mm² up to 35 mm², with a recommended tightening torque of 2.5 to 3.5 N·m. Combined terminals top and bottom mean you can feed through or loop out without separate busbar connectors.