Depth is 76 mm (70 mm installation depth), so it clears standard 80 mm deep enclosures without a gland-plate conflict.
Tripping characteristic and ratings
D-curve means magnetic-only tripping — no thermal bimetal. It handles inrush from motor starters, transformers, or capacitive loads without nuisance trips. Rated 20 A continuous at 440 V single- or multi-phase AC, with a maximum DC operating voltage of 72 V. Breaking capacity under UL 1077 / CSA C22.2 No. 235 is 5 kA — check your panel SCCR if using it in a North American branch circuit application.