Skip to main content
Siemens 5SY8240-7 — 2-Pole MCB (DIN Rail)

Siemens SENTRON 5SY8240-7 MCB, 2P C-curve, 25 kA IEC

MPN5SY8240-7
Active

Siemens SENTRON miniature circuit breaker, 5SY8240-7, 2-pole, C tripping characteristic, 25 kA breaking capacity at 400 V AC per IEC 60947-2, 36 mm wide, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SY8240-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY8240-7 — Electrical
ParameterValue
Number of poles2
5SY8240-7 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY8240-7 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY8240-7 — Environmental
ParameterValue
Pollution degree3
5SY8240-7 — Specifications
ParameterValue
At AC rated value400 V
With single-phase operation at AC rated value440 V

Product details

Rated for 400 V AC (60 V DC per pole), it delivers a 25 kA breaking capacity per IEC 60947-2 at 400 V AC — enough to handle high-fault-current industrial feeds. Under UL 1077 it's rated 5 kA, so it qualifies as a supplementary protector for North American panels. The DC rating drops to 15 kA at 60 V, which covers most control-circuit DC buses.

The 15 kA DC rating at 60 V covers most 24 V and 48 V DC control circuits, but note the 72 V DC maximum operating voltage — don't exceed that on a DC bus. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz, so it's fine on machine-mounted panels near conveyors or compressors. Temperature range spans -40 °C to 75 °C, with humidity derating: 95% RH up to 55 °C, 55% RH at 70 °C, 35% RH at 75 °C. That's broad enough for unheated outdoor cabinets in cold climates or near hot machinery. The sealable option allows locking the handle in the OFF position for lockout/tagout compliance.

Designed to IEC / EN 60947-2 and UL 1077, plus CSA C22.2 No. 235.

Frequently asked questions

How do I get pricing and availability for 5SY8240-7?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

Will 5SY8240-7 drop into a panel specified for 5SY4140-7?

Both are 2-pole SENTRON MCBs with the same 36 mm width and DIN-rail mounting, so the footprint is identical. The key difference is breaking capacity: 5SY8240-7 carries 25 kA IEC vs the 5SY4140-7's lower rating. If the panel's fault current exceeds the lower breaker's rating, the 5SY8240-7 is a direct upgrade without rewiring.

What compliance documentation is available for 5SY8240-7?

The part is designed to IEC/EN 60947-2, UL 1077, and CSA C22.2 No. 235. It's halogen-free and silicon-free. Standard Siemens declarations (RoHS, REACH) are available through the manufacturer's documentation portal.

MPN