Skip to main content
Siemens 5SY8304-7 — 3-Pole MCB (DIN Rail)

Siemens 5SY8304-7 SENTRON MCB, 3P C-Curve, 50 kA IEC

MPN5SY8304-7
Active

Siemens SENTRON 5SY8304-7, 3-pole miniature circuit breaker, C tripping characteristic, 50 kA interrupting capacity at 400 V AC per IEC 60947-2, IP20 with conductors, 3 MW units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY8304-7 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY8304-7 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per IEC 60947-250 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY8304-7 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.3 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY8304-7 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY8304-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The 15 kA DC rating at 60 V (max 72 V) covers DC bus or battery-backed loads, though the AC rating is the headline figure for most panel builds.

Fit & Integration

Rated and marked per IEC / EN 60947-2 and UL1077, covering both international and North American installations. Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6 (±1 mm at 5–25 Hz; 50 m/s² at 25–150 Hz). Mechanical service life typical 10 000 operating cycles.

Frequently asked questions

Where can I buy 5SY8304-7 and how do I get a price?

This part is available to order through independent distribution. Submit an RFQ for current pricing and availability; confirmation is provided at quote time.

What is the interrupting capacity of 5SY8304-7?

50 kA at 400 V AC per IEC 60947-2, and 15 kA at 60 V DC per the same standard. Under UL 1077 the rating is 5 kA.

What compliance documentation does this brand provide for 5SY8304-7?

The MCB carries IEC / EN 60947-2 and UL1077 certifications. It is halogen-free and silicon-free.

MPN