It also carries a UL 1077 listing (5 kA at 400 V AC), so it qualifies as a supplementary protector in North American panels where the branch circuit already has a listed OCPD upstream.
Depth is 76 mm (70 mm installation depth).
Environment and derating
Rated for ambient temperatures from -40 °C to 75 °C, but the surrounding air's relative humidity matters: max 95% up to 55 °C, tapering to 35% at 75 °C. That's the manufacturer's derating curve for internal arc quenching — if your panel sits in a hot, humid mill environment, factor that in. IP20 with connected conductors — finger-safe terminals when wired, but not protected against dripping water or dust ingress. Sealable cover allows a lockout/tagout hasp to be fitted — required on some safety circuits to prevent an unauthorized restart.