The 13 A rating holds at 45 °C ambient; at 50 °C it derates to 12.68 A, and at 55 °C to 12.34 A — so if your panel runs hot, the actual trip threshold drops. The D-curve trips magnetically between 10× and 20× In, which is the right range for motor-start and heavy inductive loads. For DC circuits, the breaking capacity sits at 15 kA per IEC 60947-2; for UL 1077 / CSA C22.2 No. 235 applications it's 5 kA — a different standard, so check which governs your install.
Depth is 76 mm, width 54 mm (3 modular units), height 90 mm. Installation depth 70 mm. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz.