Siemens 5SY8316-8BB08 — 3-Pole MCB (DIN Rail)

Siemens 5SY8316-8BB08 SENTRON MCB, 3P, 16 A, D Curve, 30 kA

MPN5SY8316-8BB08
Active

Siemens SENTRON 5SY8316-8BB08 miniature circuit breaker, 3-pole, 16 A, D tripping characteristic, 30 kA at 400 V AC per IEC 60947-2, 3 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8316-8BB08 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry
5SY8316-8BB08 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per IEC 60947-230 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY8316-8BB08 — Electrical
ParameterValue
Rated current (AC)16 A
Rated voltage (AC, multi-phase)440 V
5SY8316-8BB08 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY8316-8BB08 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The Siemens SENTRON 5SY8316-8BB08 is a 3-pole miniature circuit breaker rated 16 A with a D tripping characteristic, meaning it is designed for loads with high inrush currents — motor starters, transformers, and welding equipment — where the magnetic trip threshold (10 to 20 times In) avoids nuisance trips on startup. Under UL 1077 and CSA C22.2 No. 235 it carries a 5 kA interrupting rating, so for North American supplementary protection applications the lower figure is the binding one. The D curve and 16 A rating suit it for motor branch circuits and other inductive loads in mechanical engineering and industrial environments. The 3-pole configuration (3P) switches all three phases simultaneously; there is no switched neutral on this unit. Rated operating voltage is 440 V AC for both single-phase and multi-phase operation. Maximum DC operating voltage is 72 V, so it is not a primary choice for DC circuits above that level.

Combined terminals at both top and bottom simplify busbar and cable routing. The breaker is sealable, allowing panel builders to lock the switch position for lockout/tagout compliance. Touch protection is integrated on the terminals.

Frequently asked questions

Where can I buy 5SY8316-8BB08 and get a price?

The 5SY8316-8BB08 is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 5SY8316-8BB08?

The 5SY8316-8BB08 has a 30 kA breaking capacity at 400 V AC per IEC 60947-2, and a 5 kA interrupting rating per UL 1077 and CSA C22.2 No. 235.

What does the D tripping characteristic mean on this breaker?

The D characteristic means the magnetic trip operates at 10 to 20 times the rated current (160 to 320 A for this 16 A unit), which is designed for loads with high inrush such as motors, transformers, and welding equipment.

MPN
5SY8316-8BB08