The D curve means magnetic trip is set at 10–20× rated current, so it avoids nuisance tripping on transformer inrush or motor start-up — standard choice for motor branch circuits and inductive loads.
Combined top and bottom terminals simplify daisy-chaining busbars.
Environmental and compliance profile
Halogen-free and silicon-free construction; complies with IEC 60947-2 and UL 1077, with a UL 1077 / CSA C22.2 No. 235 interrupting rating of 5 kA.
Vibration and mechanical endurance
Vibration tested per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — suitable for installation on machinery with moderate vibration, like conveyor drives or compressor skids. Mechanical life of 10 000 operating cycles typical — not a frequent-switching device, but adequate for its role as a backup overcurrent protector behind a contactor.