The D curve holds through those surges and clears only on a sustained overload or short circuit. Breaking capacity is 40 kA at 440 V AC per IEC 60947-2 (the industrial standard, not the residential EN 60898), and 15 kA at 72 V DC.
Thermal derating and environment
Rated 10 A at 45 °C ambient; derates to 9.75 A at 50 °C and 9.49 A at 55 °C.