Skip to main content
Siemens 5SY8415-8 — 4-Pole MCB (DIN Rail)

Siemens SENTRON 5SY8415-8 MCB, 4P, 1.6 A, D curve, 70 kA

MPN5SY8415-8
Active

Siemens SENTRON 5SY8415-8 miniature circuit breaker, 4-pole, 1.6 A rated current, tripping characteristic D, 70 kA breaking capacity per IEC 60947-2, 50/60 Hz AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8415-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY8415-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC1.6 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY8415-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity, per IEC 60947-270 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY8415-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY8415-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The Siemens SENTRON 5SY8415-8 is a 4-pole miniature circuit breaker rated 1.6 A with tripping characteristic D, designed for AC systems at 50/60 Hz. Rated 1.6 A at 45 °C ambient, derated to 1.57 A at 50 °C and 1.53 A at 55 °C — so no margin squeeze in a warm enclosure if you stay within the thermal derating curve. The 4-pole construction (4P, no switched neutral) means all four poles protect the three phases and one neutral; if your panel requires a separate neutral bar, note the absence of integral neutral switching.

IP20 with connected conductors; install behind a panel door or inside a cabinet to keep the live terminals out of reach.

Environmental and compliance profile

Rated for -40 °C to 75 °C ambient, with humidity tolerance up to 95% at 55 °C. Halogen-free and silicon-free construction means no corrosive off-gassing in a sealed enclosure — relevant for panels in clean rooms or near sensitive electronics. Degree of pollution 3 (conductive pollution typical in industrial environments) and overvoltage category III (fixed installation, not downstream of a transformer). Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — survives the vibration on a machine skid.

Frequently asked questions

Where can I buy 5SY8415-8 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the difference between 5SY8415-8 and 5SY4140-7?

The 5SY4140-7 is a 4-pole, 40 A, C-curve MCB — a different rating class altogether. The 5SY8415-8 is a 1.6 A D-curve unit. They share the same SENTRON 5SY platform and 4-pole form factor, but the 5SY8415-8 is sized for small motor or transformer protection, not a general-purpose feeder circuit. They are not direct substitutes; the choice depends on the load's inrush profile and required ampacity.

What is the depth of 5SY8415-8?

Depth is 76 mm, with an installation depth of 70 mm. The unit occupies 4 modular width units (72 mm) on a DIN rail.

What compliance documentation does Siemens provide for 5SY8415-8?

The MCB carries IEC 60947-2 ratings (70 kA breaking capacity) and UL 1077 / CSA C22.2 No. 235 supplementary protector listing (5 kA). It is halogen-free and silicon-free per the spec. For RoHS/REACH declarations, refer to the manufacturer's compliance documents — the standard SENTRON declaration package applies.