It carries a 20 kA breaking capacity at 400 V AC per IEC 60947-2 and 5 kA per UL 1077, with a DC rating of 15 kA at 60 V. Rated operating voltage is 400 V AC (440 V max multi-phase or single-phase), and DC rated voltage is 60 V (72 V max).
D-curve and breaking capacity — the so-what
The D characteristic means the breaker trips at 10–20× rated current, which suits loads with high starting surges — motor starters, welding equipment, or transformer primaries — without nuisance trips. At DC, the 15 kA rating at 60 V covers common industrial DC bus applications. The 5 kA UL 1077 rating makes it acceptable for UL-listed panels in North American installations.
Snaps onto DIN rail via a quick-assembly system, any mounting position. Depth is 76 mm (70 mm installation depth). Combined terminals on top and bottom simplify wiring. Sealable, halogen-free, silicon-free — meets clean-room and low-smoke requirements. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz.