The 2-pole form factor with neutral conductor switching (1P+N) occupies 2 modular-width units (36 mm) on the DIN rail, and the 76 mm depth leaves clearance for standard enclosure depths. Rated current derates with ambient temperature: 2 A at 45 °C, 1.95 A at 50 °C, 1.9 A at 55 °C. For a panel running at 50 °C, the continuous load should not exceed 1.95 A per pole to stay within the thermal curve. The D-curve also carries a DC breaking capacity of 15 kA per IEC 60947-2, relevant for DC link or battery-backed circuits.
Deployment context
Snap-on mounting to a DIN rail in any orientation, with quick-assembly system fastening.
The 5SY8502-8 carries approvals per IEC 60947-2 (70 kA breaking capacity), UL 1077 and CSA C22.2 No. 235 (5 kA), and is halogen-free and silicon-free. The manufacturer provides RoHS and REACH compliance documentation on request.