Siemens 5SY8506-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY8506-8 SENTRON MCB, D-Curve, 50kA IEC, 2-Pole 1P+

MPN5SY8506-8
Active

Siemens SENTRON 5SY8506-8, miniature circuit breaker, D-curve, 2-pole 1P+N, 50 kA at 230 V AC per IEC 60947-2, 36 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY8506-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY8506-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY8506-8 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8506-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

D-curve 50 kA breaker for high-inrush industrial loads

The Siemens SENTRON 5SY8506-8 is a 2-pole (1P+N) miniature circuit breaker with a D tripping characteristic, rated 50 kA at 230 V AC per IEC 60947-2. On the DC side it breaks 15 kA at 60 V (max 72 V), and under UL 1077 / CSA C22.2 No.235 it's rated 5 kA — so for a North American panel that follows UL 508A, the SCCR contribution is 5 kA at 250 V AC single-phase. The neutral is switched (1P+N), which simplifies isolation on single-phase sub-circuits where you want the neutral opened with the phase.

Panel fit and environmental tolerance

Dimensions are 90 mm height, 36 mm width, 76 mm depth (70 mm installation depth). Operating temperature spans -40 °C to 75 °C, with humidity derating: max 95% RH at 55 °C, dropping to 35% at 75 °C. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz — it holds up on a machine frame or near a conveyor drive without loosening.

Frequently asked questions

What is the breaking capacity of 5SY8506-8?

50 kA at 230 V AC per IEC 60947-2; 15 kA at 60 V DC per IEC 60947-2; 5 kA at 250 V AC per UL 1077 / CSA C22.2 No.235.

What is the difference between 5SY8506-8 and 5SY4140-7?

The 5SY4140-7 is a different rating within the same SENTRON 5SY family. The 5SY8506-8 is a D-curve 2-pole 1P+N breaker with 50 kA breaking capacity; the 5SY4140-7 has a different current rating and tripping characteristic. They share the same 36 mm width, DIN-rail mount, and IEC/UL certifications, so a panel designed for one can accept the other without mechanical modification — but the protection curve and interrupting rating must match the circuit design.

Where can I buy 5SY8506-8?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.