Deployment context
IP20 with connected conductors — fine inside a closed cabinet, not for washdown. Ambient range -40 to 75 °C, but derate above 55 °C per the humidity curve (95% RH at 55 °C, 55% at 70 °C, 35% at 75 °C). Vibration tested to IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — survives typical machine-mount vibration.
This is a current-production part (lifecycle stage: current). No successor or phase-out notice.