Skip to main content
Siemens 5SY8515-7 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SY8515-7 MCB, 1P+N, C-curve, 1.6 A, 70 kA

MPN5SY8515-7
Active

Siemens SENTRON 5SY8515-7, miniature circuit breaker, 1P+N, C-curve, 1.6 A rated current, 70 kA at 230 V AC per IEC 60947-2, 5 kA per UL 1077, 36 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8515-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityMechanical engineering / industry
5SY8515-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY8515-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8515-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SY8515-7 is a 1P+N miniature circuit breaker with a C-curve tripping characteristic, rated 1.6 A at 230 V AC. It switches the neutral conductor along with the phase, which matters for installations where full isolation is required on both poles. For DC circuits, it's rated 15 kA up to 72 V, so it also handles battery-backed or rectifier-fed loads.

The sealable feature lets you lock the handle position for lockout/tagout on the line side.

Rated for ambient temperatures from -40 °C to 75 °C, with humidity influence capped at 95% up to 55 °C, derating to 35% at 75 °C. Halogen-free and silicon-free construction, which is often a spec for clean-room or semiconductor-adjacent panels. The lifecycle status is current production (active).

Approvals and standards

Rated under IEC 60947-2 (70 kA at 230 V AC, 15 kA at 72 V DC) and UL 1077 / CSA C22.2 No. 235 (5 kA at 230 V AC). The part carries the IEC 81346-2 designation F for protective devices. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz.

Frequently asked questions

Where can I buy 5SY8515-7 and how do I get a price?

The part is available to order through this listing. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the closest functional second-source for 5SY8515-7?

The 5SY7210-7CC is a 1P+N C-curve MCB but with a different current rating and breaking capacity. It will not drop into the same panel without checking the load and fault current requirements — the 5SY8515-7 is the correct part for a 1.6 A, 70 kA spec.

What compliance documentation does Siemens provide for 5SY8515-7?

The part is rated under IEC 60947-2 and UL 1077 / CSA C22.2 No. 235. It is halogen-free and silicon-free, which supports RoHS/REACH compliance. Full declarations are available on request.

MPN