Skip to main content
Siemens 5SY8516-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY8516-7 SENTRON MCB, 2-Pole C-Curve, 30kA IEC

MPN5SY8516-7
Active

Siemens SENTRON 5SY8516-7 miniature circuit breaker, 2-pole (1P+N), C-curve, 30 kA per IEC 60947-2, 230 V AC, 60 V DC, IP20, active production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8516-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY8516-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY8516-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8516-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The 1P+N pole configuration (2 physical poles) with neutral conductor switching makes it suitable for single-phase AC circuits where the neutral needs to be disconnected simultaneously with the phase. Rated at 230 V AC (50/60 Hz) and 60 V DC (max 72 V), it covers standard industrial supply voltages.

Standards and approvals — what they certify

Listed to IEC / EN 60947-2 (the low-voltage switchgear standard for industrial applications) and UL 1077 (supplementary protectors for North America). The UL 1077 path gives a 5 kA interrupting rating at 250 V AC single-phase — enough for most panelboard supplementary protection, but lower than the IEC 30 kA figure. The DC rating per IEC 60947-2 is 15 kA at 60 V.

Sealable terminals (top and bottom combined) allow tamper-proofing after commissioning.

Environmental range and derating

Rated for ambient temperatures from -40 °C to +75 °C, with humidity derating: max 95% RH up to 55 °C, tapering to 35% at 75 °C. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz — sufficient for most industrial machinery and conveyor lines.

Frequently asked questions

Where can I buy 5SY8516-7 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery window.

Will 5SY8516-7 drop into a panel designed for 5SY4140-7?

Both are 2-module-width SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The key difference is the breaking capacity: 5SY8516-7 carries 30 kA per IEC 60947-2 versus the 5SY4140-7's lower rating — verify the fault level at the installation point before substituting.

What compliance documentation does Siemens provide for 5SY8516-7?

The MCB is certified to IEC / EN 60947-2 and UL 1077. It is halogen-free and silicon-free. Standard documentation includes the declaration of conformity (CE/UKCA), UL recognition file, and material compliance data per RoHS/REACH — request these with your RFQ.

MPN