Siemens 5SY8604-7 — 4-Pole MCB (DIN Rail)

Siemens 5SY8604-7 SENTRON MCB, 4 A, C-Curve, 4-Pole, 50 kA

MPN5SY8604-7
Active

Siemens SENTRON 5SY8 series, miniature circuit breaker, 4 A, C-curve, 4-pole (3P+N), 400 V AC, 50 kA breaking capacity, 72 mm wide (4 MW).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8604-7 — Identification
ParameterValue
Type / order code5SY8
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY8604-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC4 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY8604-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity, per IEC 60947-250 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY8604-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY8604-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY8604-7 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Siemens 5SY8604-7 — 4 A C-Curve MCB, 4-Pole, 50 kA

The Siemens 5SY8604-7 is a SENTRON miniature circuit breaker rated 4 A with a C tripping characteristic, 4 poles (3P+N), and a 50 kA breaking capacity at 400 V AC per IEC 60947-2. This is a current-production part in the 5SY8 design series, suitable for panel building and industrial distribution.

The 4 A rated current with C-curve means it trips at 5 to 10 times rated current (20–40 A magnetic release), covering motor-start and transformer inrush without nuisance trips. The DC breaking capacity is 15 kA per IEC 60947-2, and under UL 1077 / CSA C22.2 No.235 it carries a 5 kA interrupting rating. The 4-pole (3P+N) configuration protects all three phases and switches the neutral, common in 3-phase 4-wire systems (TN-C-S, TN-S) where the neutral must be disconnected for isolation.

Mounting and wiring — fits standard DIN rail

Snap-on mounting to DIN rail EN 60715, 72 mm wide (4 width units of 18 mm). The 76 mm depth (70 mm installation depth) fits standard enclosures with 80 mm deep gland plates. Conductor cross-section accepts 0.75 to 35 mm² solid or stranded; tightening torque 2.5 to 3.5 N·m with screw terminals. Combined top and bottom terminals simplify daisy-chaining busbars. Ambient temperature range -25 to +55 °C; storage -40 to +75 °C. Mounting position any, which helps in tight enclosures.

Rated per IEC 60947-2 (50 kA at 400 V AC, 15 kA DC) and UL 1077 / CSA C22.2 No.235 (5 kA). Overvoltage category III. Halogen-free and silicon-free construction. Sealable — allows lockout/tagout for maintenance isolation. Touch protection integrated.

Frequently asked questions

What is the breaking capacity of 5SY8604-7?

50 kA at 400 V AC per IEC 60947-2, 15 kA DC per IEC 60947-2, and 5 kA per UL 1077 / CSA C22.2 No.235.

What conductor sizes does 5SY8604-7 accept?

Solid or stranded conductors from 0.75 mm² up to 35 mm², with a tightening torque of 2.5 to 3.5 N·m.

Where can I buy 5SY8604-7 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.