What this MCB does on the rail
For UL 1077 / CSA C22.2 No. 235 installations it carries a 5 kA interrupting rating, so check the panel SCCR if you are in a North American spec.
The 25 A rating holds at 45 °C ambient. At 50 °C it derates to 24.38 A; at 55 °C to 23.72 A. The operating range spans -40 °C to 75 °C, with humidity constraints: 95% RH up to 55 °C, 55% RH up to 70 °C, 35% RH up to 75 °C. Vibration resistance per IEC 60068-2-6 is ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz — suited for machine-mounted enclosures.