SENTRON 5SY8640-8 — D-curve MCB, 40 A, 4-pole
Rated 40 A at 45 °C, it derates to 38.76 A at 50 °C and 37.48 A at 55 °C, so panel ambient must be considered when loading near the limit. Breaking capacity is 25 kA at AC per IEC 60947-2, 15 kA at DC per IEC 60947-2, and 5 kA at AC per UL 1077 and CSA C22.2 No. 235.
Installation depth 70 mm; overall depth 76 mm. Sealable design allows panel lockout for isolation procedures.
Operating temperature range -40 to 75 °C, with humidity derating: max 95% RH at 55 °C, 55% at 70 °C, 35% at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz. Halogen-free and silicon-free construction. Suitable for mechanical engineering and industry applications per manufacturer designation. Listed under IEC 81346-2 and DIN EN 61346-2 function code F (protective device).