Skip to main content
Siemens 6AG1040-1LA00-2AA0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1040-1LA00-2AA0 CU310-2 DP, -20…+55 °C

MPN6AG1040-1LA00-2AA0
Active

Siemens SIPLUS S120 Control Unit CU310-2 DP (6AG1040-1LA00-2AA0), –20…+55 °C, PROFIBUS, conformal coated, 11 DI / 1 AI.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1040-1LA00-2AA0 — I/O
ParameterValue
Digital inputs11; According to IEC 61131-2 type 1, 5 floating digital inputs, 8 bidirectional non-floating digital inputs/outputs, 3 parameterizable failsafe digital inputs (electrically isolated) or, alternatively, 6 parameterizable digital inputs (electrically isolated)
6AG1040-1LA00-2AA0 — Environmental
ParameterValue
Temperature, min.-20 °C; = Tmin
Temperature, max.55 °C; = Tmax
6AG1040-1LA00-2AA0 — Mechanical
ParameterValue
Width73 mm
Height191 mm
Depth75 mm

Product details

The 6AG1040-1LA00-2AA0 is a Siemens SIPLUS S120 Control Unit CU310-2 DP — a drive controller for SINAMICS S120 systems with PROFIBUS interface and an extended temperature range from –20 to +55 °C. It accepts a 0.3 A max load from the 24 V power module or external supply (20.4–28.8 V).

The front end carries 11 digital inputs (IEC 61131-2 type 1): 5 floating, plus 8 bidirectional non-floating DI/DO. Three of those can be parameterized as failsafe inputs, or six as isolated digital inputs. One differential analog input doubles as a supplementary digital input. PROFIBUS DP is the only fieldbus on board; there are zero PROFINET interfaces. If the design calls for PN, this isn't the control unit you want — it's a different order code in the family. Terminal capacity: signal lines 0.05–1.5 mm², AWG 30–16. Strip length isn't given, but usual practice with spring-cage (not confirmed) — verify against the mating connector datasheet.

Mounting and derating

Dimensions 191 × 73 × 75 mm (H×W×D), IP20 rated. Above 1 000 m altitude, derate 3 K per 1 000 m on the ambient temperature. Maximum power loss is 20 W. With V/f control without encoder supported (not vector with encoder), this control unit fits standard S120 drive configurations where encoderless vector or V/f is adequate.

Conformal coating and extended temperature qualification (storage –40 to +70 °C) mean it's intended for the Siemens SIPLUS harsh-environment line, but it remains a standard catalog item. For the BOM, that's a clean MRO cross-reference: if you spec 6SL3040-1LA00-0AA0, this is the ruggedized swap with the same footprint and PROFIBUS connection. Available quoted to order via RFQ. No lead-time number here — quantity and schedule determine that. If you need a PCN or environmental compliance package (ISA/ANSI, IPC conformal coating, RoHS/REACH statements), they're part of the standard Siemens documentation for SIPLUS products; request them with the RFQ.

Frequently asked questions

What is the maximum and minimum operating temperature?

Rated for –20 to +55 °C ambient. Above 1 000 m altitude, derate 3 K per 1 000 m. Storage temperature is –40 to +70 °C.

What compliance documentation does this part carry?

Conformal coating per IPC-CC-830A Class A and environmental resistance to ANSI/ISA-71.04 Level GX Group A/B (excluding trichlorethylene), Level LC3 salt spray, Level LB3 oil. IP20 enclosure. Siemens standard documentation (RoHS, REACH, CE) is available on request.

MPN
6AG1040-1LA00-2AA0