This is the ruggedized SIPLUS version of the LOGO! 24CE — order code 6AG1052-1CC08-7BA1 — with conformal coating and extended temperature range. It’s based on the standard 6ED1052-1CC08-0BA1 but hardened for environments where condensation, coolant mist, or salt spray are present. The display is readable across 0 to 55 °C; outside that band the contrast may drop but reverses on return to normal temperature. That matters if the panel lives near a washdown zone or unheated enclosure.
Mounting and integration notes
Snaps onto 35 mm DIN rail, 71.5 mm wide, 90 mm tall, 60 mm deep. That’s equivalent to 4 standard module widths — same footprint as the basic LOGO! 24CE. Eight digital inputs, of which four can be configured as analog (0–10 V). Four transistor outputs, each rated 0.3 A at up to 55 °C, short-circuit protected electronic (1 A threshold). Cold restart is allowed down to -20 °C, including condensation — but don’t commission it while condensation is present.