Skip to main content
Siemens 6AG1052-1HB00-7BA8 — PLCs (Programmable Logic Controllers)

Siemens SIPLUS LOGO! 24RCE 6AG1052-1HB00-7BA8, -40 to 70°C

MPN6AG1052-1HB00-7BA8

Siemens SIPLUS LOGO! 24RCE, 6AG1052-1HB00-7BA8, Logic Module, 8 DI, 4 Relay DO, Display, Ethernet, -40 to 70°C, conformal coating, 24V AC/DC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1052-1HB00-7BA8 — I/O
ParameterValue
Digital inputs8
Digital outputs4; Relays
6AG1052-1HB00-7BA8 — Electrical
ParameterValue
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Short-circuit protectionNo; external fusing necessary
6AG1052-1HB00-7BA8 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1052-1HB00-7BA8 — Mechanical
ParameterValue
Width71.5 mm
Height90 mm
Depth60 mm

Product details

What it is: rugged LOGO! for dirty, hot, or cold cabinets

The Siemens 6AG1052-1HB00-7BA8 is a SIPLUS version of the standard LOGO! 24RCE (6ED1052-1HB00-0BA8), factory-fitted with conformal coating and rated for -40 to 70°C ambient, with cold start at -20°C. The display is usable down to 0°C and up to 55°C; outside that range it may be slow or hard to read, but the module keeps running and recovers when temperature returns to normal. At -40°C you rely on remote access or datalog, not the local screen.

Wiring and protection notes

Short-circuit protection is not built in; external fusing necessary. Relay outputs handle 10 A resistive or 3 A inductive max. Resistant to commercially available coolants and lubricants including diesel and oil droplets — a practical choice for machine-tool or engine-test stands where standard controllers would need a sealed enclosure.

What you won't find on the spec sheet

The 480-hour power reserve means the program and real-time clock survive a weekend-plus power outage without a battery. Ethernet with built-in web server and datalogging allows remote monitoring without an extra gateway.

Frequently asked questions

Does this module have built-in short-circuit protection on the outputs?

No, there is no short-circuit protection; external fusing or circuit breakers must be provided on the 24V supply and on each relay output group.

Can I use 24V AC and 24V DC on the same module?

Yes, it accepts both 24V AC and 24V DC. The permissible DC range is 20.4 to 28.8 V; for AC the frequency must be between 47 and 63 Hz.

MPN