Skip to main content
Siemens 6AG1052-2MD00-7BA8 — PLCs (Programmable Logic Controllers)

Siemens 6AG1052-2MD00-7BA8 SIPLUS LOGO!, -40 to 70°C

MPN6AG1052-2MD00-7BA8

Siemens SIPLUS LOGO! 12/24RCEO logic module, 12/24 V DC supply, 8 digital inputs (4 analog-capable), 4 relay outputs, Ethernet with web server, -40 to +70 °C, conformal coated.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1052-2MD00-7BA8 — I/O
ParameterValue
Digital inputs8; Of which 4 can be used in analog mode (0 to 10 V)
Digital outputs4; Relays
6AG1052-2MD00-7BA8 — Electrical
ParameterValue
Permissible range, lower limit (DC)10.8 V
Permissible range, upper limit (DC)28.8 V
Short-circuit protectionNo; external fusing necessary
6AG1052-2MD00-7BA8 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-40 °C
Temperature, max.70 °C
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1052-2MD00-7BA8 — Mechanical
ParameterValue
Width71.5 mm
Height90 mm
Depth58 mm

Product details

What the -40 to +70 °C range means for deployment

The 6AG1052-2MD00-7BA8 operates from -40 to +70 °C with conformal coating. The conformal coating protects against condensation, coolant mist, and oil droplets in the air — a common requirement in machine-tool and packaging-line environments where the standard module would fail from creepage tracking.

I/O count and analog capability

The module provides 8 digital inputs, of which 4 can be configured in analog mode (0 to 10 V). This means a single unit can handle four 0-10 V sensors (pressure transducers, potentiometers, level sensors) without an additional analog expansion module — saving a DIN-rail slot and the cost of a separate I/O block. The 4 relay outputs are rated 10 A resistive and 3 A inductive per channel. The inductive rating matters for driving small contactors, solenoid valves, or motor starters directly; the resistive rating covers heater contactors and indicator loads. Note that short-circuit protection is external — each output circuit needs its own fuse or breaker.

Ethernet, web server, and data logging built in

The 6AG1052-2MD00-7BA8 includes an integrated Ethernet port with a web server and data-logging function. That means you can monitor the module's I/O states, change parameters, and retrieve logged data through a standard browser without a programming cable or dedicated HMI — useful for remote cabinets or commissioning checks. The logic module is programmable with LOGO! Soft Comfort V8 or higher, and older projects are executable. The 400-block memory handles small machine sequences.

DIN-rail footprint and power supply

The 90 mm height and 58 mm depth fit standard 120 mm deep enclosures. The 12/24 V DC supply range (10.8 to 28.8 V DC) means it runs on the same 24 V DC bus as sensors and actuators — no separate power rail needed. A 480-hour power reserve keeps the real-time clock and retentive data alive during a mains outage — enough to bridge a weekend shutdown without battery replacement.

No stock-holding claim; each order is sourced per the BOM quantity.

Frequently asked questions

Does 6AG1052-2MD00-7BA8 have Ethernet and web server?

Yes, the module includes an integrated Ethernet port with a web server and data-logging function. It can be monitored and configured through a standard browser without additional software or HMI hardware.

MPN