6AG1055-1MB00-2XB1 SIPLUS LOGO! DM8 12/24R, 70°C

MPN6AG1055-1MB00-2XB1

SIPLUS LOGO! DM8 12/24R, spare part based on 6ED1055-1MB00-0BA1, 4 digital inputs, 4 relay outputs, DC 12/24 V, -25 to +70 °C, 2 DU wide on DIN rail.

$439.98Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6AG1055-1MB00-2XB1 — I/O
ParameterValue
Digital inputs4
Digital outputs4; Relays
6AG1055-1MB00-2XB1 — Electrical
ParameterValue
Permissible range, lower limit (DC)10.8 V; 11 V @ >55 °C
Permissible range, upper limit (DC)28.8 V; 27.5 V @ >55 °C
Short-circuit protectionNo
6AG1055-1MB00-2XB1 — Environmental
ParameterValue
Temperature, min.-25 °C; = Tmin
Temperature, max.70 °C; = Tmax; 55 °C @ UL/cUL use
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1055-1MB00-2XB1 — Mechanical
ParameterValue
Width36 mm; 2 DU
Height90 mm
Depth55 mm

Product details

Temperature range and derating

The 6AG1055-1MB00-2XB1: This module lives where standard LOGO! units won't: ambient -25 to +70 °C. Under UL/cUL use (File E120869) the max drops to 55 °C. The input voltage range also narrows above 55 °C: 11–27.5 V DC instead of the full 10.8–28.8 V DC. Output relay rating changes too — 3 A resistive per relay above 55 °C (normally 5 A), and inductive loads drop to 1 A per relay above that threshold (3 A below). Keep these curves in mind if you're stuffing this into a hot panel with forced convection.

Compliance conformance for cross-border shipment

The module carries UL recognition (E120869) and is rated Limit class B for residential-area use. No FM, CSA, or marine approval — verify local codes if those are required.

Mounting and wiring field note

Resistive load max 5 A per relay (10 A total), inductive max 3 A; no short-circuit protection — external fusing assumed; inputs: 4 digital, sink/source.

Frequently asked questions

What are the max and min operating temperatures?

It runs from -25 °C to +70 °C. Under UL/cUL use, the max is 55 °C.

Will this module drop into a panel designed for 6ED1052-1MD00-0BA6?

No. The 6ED1052 is 4 DU wide with a display and 8 digital inputs; this module is 2 DU wide with no display and 4 inputs. They are not footprint- or I/O-compatible without rewiring and panel repunching.