6AG1131-6BF01-7BA0 Siemens SIPLUS ET 200SP DI 8x24V DC Digital Input Module

MPN6AG1131-6BF01-7BA0
Active

Siemens, 6AG1131-6BF01-7BA0, SIPLUS ET 200SP digital input module, 8 channels, 24 V DC, P-reading, 15 x 73 x 58 mm, BU type A0 base unit, parameterizable diagnostics, active lifecycle.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1131-6BF01-7BA0 — I/O
ParameterValue
Digital inputs8
Input data area1 byte; + 1 byte for QI information
6AG1131-6BF01-7BA0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1 W; 24 V, 8 inputs supplied via encoder supply
Short-circuit protectionYes
6AG1131-6BF01-7BA0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1131-6BF01-7BA0 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)28 g

Product details

Input thresholds and wiring compatibility

The module supports 2-wire sensors natively. Three-wire connections work with the same BU type A0 base unit; four-wire sensors need the additional potential distributor module alongside BU type A0.

Diagnostics and parameterization

Module-wide wire-break and short-circuit detection is built in. A diagnostic alarm fires when a fault is detected. The module is parameterizable, meaning you can enable or suppress diagnostics per the application needs. I&M data (I&M0 to I&M3) is supported for asset identification in larger plants. Input filter times are configurable from 0.05 ms to 20 ms (both rise and fall). Use the slower end in noisy environments to debounce; stay at the fast edge for high-speed sensor signals where the maximum cable length still supports it.

Mounting and base unit selection

Physical footprint: 15 mm wide, 73 mm high, 58 mm deep. The base unit supports automatic encoding, eliminating addressing dip switches. No firmware update capability; field replacement is a mechanical swap with the same base unit.

Frequently asked questions

What is the typical signal current for a '1' input?

The typical current draw at signal '1' is 2.5 mA at the 24 V nominal rail.