Skip to main content
Siemens 6AG1131-6BH01-7BA0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1131-6BH01-7BA0 Digital Input Module, 16 Ch, 24 V

MPN6AG1131-6BH01-7BA0
Active

Siemens 6AG1131-6BH01-7BA0 S7-1200 digital input module, 16 channels, 24 VDC, current production, 15 mm wide.

$124.46Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1131-6BH01-7BA0 — I/O
ParameterValue
Digital inputs16
Input data area2 byte; + 2 bytes for QI information
6AG1131-6BH01-7BA0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1.7 W
6AG1131-6BH01-7BA0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1131-6BH01-7BA0 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)28 g

Product details

Siemens 6AG1131-6BH01-7BA0 is a 16-channel digital input module rated 24 VDC with per-channel wire-break diagnostics. It is a current-production part — no last-time-buy constraints. Inputs occupy 2 bytes in the process image plus 2 bytes for quality information (QI). Voltage thresholds are -30 to +5 V for signal '0' and +11 to +30 V for signal '1', with a typical draw of 2.5 mA per channel at 24 VDC. The module supports 2-wire sensors, parameterizable input delays (0.05 ms to 20 ms), and accepts cables up to 1 000 m shielded or 600 m unshielded. Each channel can be individually diagnosed for wire breaks using an optional 25–45 kΩ pull-up circuit.

Mounts on BU type A0 base units. Width is 15 mm per module — a slim profile that stacks efficiently on DIN rail. For 2-wire sensors, the module alone suffices; for 3- or 4-wire connections, add a potential distributor module on the same base unit. No isochronous mode, no oversampling, and no cross-channel interference between inputs. Automatic encoding via the backplane bus handles addressing; no DIP-switch configuration required.

Frequently asked questions

What does MSI (No) mean?

MSI stands for motor starter interface. This module does not support MSI; it is a standard digital input module for sensor and switch signals only.

MPN
6AG1131-6BH01-7BA0