Skip to main content
Siemens 6AG1131-6TF00-7CA0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1131-6TF00-7CA0 SIPLUS DI Module, 8x 8.2V NAMUR

MPN6AG1131-6TF00-7CA0
Active

Siemens SIPLUS 8-channel digital input module, 6AG1131-6TF00-7CA0, 8.2 V DC NAMUR, wire-break and short-circuit diagnostics, active production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1131-6TF00-7CA0 — I/O
ParameterValue
Digital inputs8; NAMUR
6AG1131-6TF00-7CA0 — Electrical
ParameterValue
Rated value (DC)8.2 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1.5 W
Short-circuit protectionNo
6AG1131-6TF00-7CA0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Operating temperature, max. (horizontal mounting)70 °C; = Tmax; > +60 °C number of simultaneously controllable inputs max. 4 (no adjacent points)
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1131-6TF00-7CA0 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)32 g

Product details

The Siemens 6AG1131-6TF00-7CA0 is an 8-channel digital input module for 8.2 V DC NAMUR sensors. It reports wire-break and short-circuit per channel. Signal thresholds: a logic 0 sits between 0.35 and 1.2 mA, logic 1 typically draws 8 mA. This matches NAMUR proximity pickups used in hazardous-area or harsh-environment installations. Diagnostics cover wire-break, short-circuit, and a group error LED. You can also enable channel-by-channel diagnostic alarms and hardware interrupts, plus pulse extension up to 2 s for fluttery mechanical contacts.

Integration notes

Mounts on BU type A0 base units; dimensions 15 mm wide × 73 mm high × 58 mm deep. Isolation tested at 707 V DC type test. Power draw is 1.5 W typical from the backplane. No isochronous mode; no MSI or counter function.

Sourcing note

Listed as current production.

Frequently asked questions

What diagnostics does this module support?

Wire-break and short-circuit detection channel by channel, a group error LED, diagnostic alarms, and parameterizable hardware interrupts.