Panel Integration Brief
Wire-break and short-circuit detection are channel-granular and can be separately enabled or disabled via diagnostics functions. The group error SF LED gives a visual summary. Outputs respond to CPU/memory STOP by substituting a value or holding the last valid state. Shielded cable run up to 1 000 m, unshielded up to 600 m. Power loss typ. 1.4 W.
Switching Performance
Resistive load switching up to 100 Hz; inductive load limited to 2 Hz with 0.5 H; lamp load max 10 Hz. Transition times: 0 → 1 at 100 µs, 1 → 0 at 400 µs. Reverse polarity protection is present when sharing the load voltage with the power module.