Skip to main content
Siemens 6AG1132-4HB13-2AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1132-4HB13-2AB0 SIPLUS 2DO Relay, 5A, -40/+60°C

MPN6AG1132-4HB13-2AB0

SIPLUS ET 200S EM 2DQ RLY 5A, 6AG1132-4HB13-2AB0, 2 relay outputs 5 A, conformally coated for -40 to +60 °C, 15 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1132-4HB13-2AB0 — I/O
ParameterValue
Digital outputs2
6AG1132-4HB13-2AB0 — Electrical
ParameterValue
Rated value (DC)24 V; From power module
Power loss (typ.)0.6 W
Short-circuit protectionNo
6AG1132-4HB13-2AB0 — Environmental
ParameterValue
Installation altitude, max.2 000 m
Temperature, min.-40 °C; = Tmin
Temperature, max.60 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
6AG1132-4HB13-2AB0 — Mechanical
ParameterValue
Width15 mm
Height81 mm
Depth52 mm
Weight (approx.)50 g

Product details

This 6AG1132-4HB13-2AB0 is a SIPLUS ET 200S electronic module carrying two relay outputs, each rated 5 A for signal '1' and 5 A thermal continuous current. It is the conformally coated, extended-temperature variant (−40 to +60 °C) of the standard 6ES7132-4HB13-0AB0.

Dimensions are 15 mm wide × 81 mm high × 52 mm deep, mounting as a standard ET 200S electronic module. Reverse polarity protection is built in on the backplane side, but the relay outputs themselves lack short-circuit protection — an external fuse or breaker per channel is required for the load circuit. No diagnostic function is present; status indication is a green LED per output. On CPU/master STOP the module can substitute a value (0 or 1, configurable) or keep the last state, which matters for fail-safe system design. Galvanic isolation exists between channels and backplane bus as well as between channels and load voltage L+, enabling mixed-load wiring in the same assembly.

Frequently asked questions

What is the operating temperature range of this module?

The module is rated for −40 to +60 °C ambient (vertical and horizontal mounting same range) with derating above 40 °C for vertical installation.

Does this module have short-circuit protection?

No, short-circuit protection is not provided on the outputs. An external fuse or circuit breaker must be used on each load circuit.

MPN
6AG1132-4HB13-2AB0