Skip to main content
Siemens 6AG1132-6BF00-7BA0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1132-6BF00-7BA0 SIPLUS DQ 8x24VDC/0.5A, 15 mm

MPN6AG1132-6BF00-7BA0

Siemens SIPLUS DQ 8x24VDC/0.5A digital output module, 15 mm width, 8 outputs, wire-break and short-circuit diagnostics, active lifecycle.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6AG1132-6BF00-7BA0 — I/O
ParameterValue
Digital outputs8; > +60 °C max. total current 1.0 A
6AG1132-6BF00-7BA0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1 W
Short-circuit protectionYes
6AG1132-6BF00-7BA0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin; Startup @ -25 °C
Operating temperature, max. (horizontal mounting)70 °C; = Tmax; > +60 °C max. total current 1.0 A
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1132-6BF00-7BA0 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)28 g

Product details

The Siemens 6AG1132-6BF00-7BA0 is an 8-channel SIPLUS digital output module for the ET 200SP platform, each channel rated 0.5 A at 24 V DC. It packs wire-break detection per channel, group error reporting, and short-circuit protection into a 15 mm-wide slice — important for dense cabinet layouts. The operating temperature spans -40 °C to +70 °C horizontally and -40 °C to +50 °C vertically, with a derating above +60 °C: total current limited to 1.0 A. That means in a warm cabinet you cannot drive all 8 channels at full load simultaneously.

Thermal headroom and diagnostic depth

Above +60 °C ambient, the module limits total output current to 1.0 A — regardless of the 0.5 A per-channel rating. For a panel running near that threshold, plan channel loading accordingly. The response threshold of 0.7 to 1.3 A triggers short-circuit detection before the output fails, and wire-break detection confirms load circuit continuity. These diagnostics, plus group error reporting, let the CPU isolate faults without additional sensors.

MPN
6AG1132-6BF00-7BA0