Siemens 6AG1132-6HD00-7BB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1132-6HD00-7BB0 4-Relay Output Module, 20 A

MPN6AG1132-6HD00-7BB0

Siemens 6AG1132-6HD00-7BB0 PLC output module, 4 relay outputs, 20 A per module, 24 V DC, 20 mm width, I&M data 0-3, active production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1132-6HD00-7BB0 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1.5 W
6AG1132-6HD00-7BB0 — Mechanical
ParameterValue
Width20 mm
Weight (approx.)40 g
6AG1132-6HD00-7BB0 — Environmental
ParameterValue
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin; Startup @ -25 °C
Operating temperature, max. (horizontal mounting)70 °C; = Tmax; > +60 °C max. continuous current per relay 3 A, max. total current module 12 A
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)

Product details

Relay output module for tight DIN-rail slots

The Siemens 6AG1132-6HD00-7BB0 is a 4-relay output module that fits a 20 mm wide DIN-rail slot — one of the narrowest footprints for a quad relay bank in the S7-1200 ecosystem. It carries a total module current of 20 A, with per-channel limits that derate with ambient temperature: 20 A up to 40 °C, 16 A at 50 °C, and 16 A at 60 °C. Above 60 °C horizontal, each relay is capped at 3 A continuous and the module total drops to 12 A.

What the ratings mean for your panel

The 20 A total module current is the sum of all relay outputs — if you run all four at 5 A each, you're at the limit. The derating above 60 °C is a hard constraint: at 65 °C horizontal, you can only pull 3 A per relay and 12 A total, so plan your load distribution accordingly. The module requires a BU type B0 base unit (sold separately) and draws 100 mA max from the 24 V DC supply without load. Reverse polarity protection is built in, and the supply voltage is monitored via a green PWR LED. I&M data 0 through 3 is supported, meaning the module reports its identity and maintenance history to the controller — useful for asset tracking in larger lines.

Lifecycle and sourcing reality

Sourced and quoted to order against your BOM quantity; availability and current pricing confirmed at RFQ time.

Frequently asked questions

What base unit does 6AG1132-6HD00-7BB0 require?

It requires a BU type B0 base unit. The base unit is ordered separately and provides the backplane connection and DIN-rail mounting.

What is the maximum current per relay at high ambient temperatures?

Up to 60 °C horizontal, each relay can carry 5 A continuous (16 A total module). Above 60 °C up to 70 °C, each relay is limited to 3 A and the module total to 12 A.

Does 6AG1132-6HD00-7BB0 support I&M data?

Yes, it supports I&M data 0 through 3, enabling identification and maintenance data exchange with the controller.

MPN
6AG1132-6HD00-7BB0