4‑way relay output module for the S7‑1500
Siemens SIPLUS S7-1500 digital output module 6AG1132-6HD00-7BB1 packs 4 relay outputs rated 5 A per channel at 24 V DC. Diagnostic alarm and group error reporting are standard, with a green LED per channel and a green/red DIAG LED for module status.
Mounting and wiring parameters
Unshielded cable runs up to 200 m; shielded up to 1 000 m. Minimum switching current is 100 mA at 5 V DC, and each channel handles inductive loads up to 2 A; module total is 20 A derated to 60 °C.