Skip to main content
Siemens 6AG1132-6HD01-7BB1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1132-6HD01-7BB1 Digital Output Module, 20 A Relay

MPN6AG1132-6HD01-7BB1
Active

Siemens 6AG1132-6HD01-7BB1 digital output module, 8 relay outputs, 20 A at 40 °C, 230 V AC / 24 V DC, 20 mm wide, for SIMATIC S7-1200.

$250.58Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1132-6HD01-7BB1 — I/O
ParameterValue
Digital outputs4
Input data area+ 1 byte for QI information
Output data area1 byte
6AG1132-6HD01-7BB1 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)55 mA; without load
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)1.5 W
Short-circuit protectionNo
6AG1132-6HD01-7BB1 — Environmental
ParameterValue
Installation altitude, max.3 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. continuous current of 3 A per relay
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 1 K/100 m) at 795 hPa ... 701 hPa (+2 000 m ... +3 000 m)
6AG1132-6HD01-7BB1 — Mechanical
ParameterValue
Width20 mm
Height73 mm
Depth58 mm
Weight (approx.)40 g

Product details

Panel fit and output capacity

The 6AG1132-6HD01-7BB1: This is an 8-channel relay output module for the SIMATIC S7-1200 system — 20 mm wide, 73 mm tall, 58 mm deep. It snaps onto the standard DIN rail in the same footprint as the CPU and other signal modules, so it shares the backplane bus without extra wiring for the I/O data. Each relay output is rated 20 A continuous up to 40 °C, derating to 16 A at 50 °C and 60 °C. That current capacity is unusual for a compact S7-1200 module — it directly drives small motors, contactor coils, or valve solenoids without an interposing relay. The outputs accept both AC (230 V rated) and DC (24 V rated) loads, with channel-to-channel isolation and a tested isolation voltage of 2,500 V DC. This means mixed-voltage wiring in the same module is safe — one channel can switch a 24 V DC pilot light while another switches a 230 V AC contactor.

Sourcing and lifecycle for the BOM line

It uses the type B0 or base unit (BU) for the S7-1200 system, which is the same mechanical interface as the standard 6ES7132-6HD01-0BB0. The 6AG1 prefix indicates the SIPLUS variant, rated for extended temperature range and harsh environments — confirm the base unit part number separately if you are replacing a standard module.

Diagnostics and wiring notes

The module provides a diagnostic alarm and a green/red DIAG LED for module-level fault indication, plus a green LED per channel for status. That is enough to isolate a failed output without a handheld meter — the DIAG LED flashes on a short-circuit or wire-break condition. Power dissipation is 1.5 W typical — negligible for cabinet thermal budgeting, but worth noting if the module sits in a sealed enclosure with other high-current relay modules. The unshielded cable run is limited to 200 m; shielded cable extends that to 1,000 m.

Frequently asked questions

What is the maximum current per channel on this relay output module?

Each relay output is rated 20 A at 40 °C, derating to 16 A at 50 °C and 60 °C. The rating applies to all mounting positions at 50 °C and above.

What base unit does 6AG1132-6HD01-7BB1 require?

It uses the type B0 or base unit (BU) from the S7-1200 system. The base unit is ordered separately and provides the terminal connections for field wiring.

MPN
6AG1132-6HD01-7BB1