Skip to main content
Siemens 6AG1134-0GB00-4AY0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-0GB00-4AY0 SITOP Battery Module 7Ah

MPN6AG1134-0GB00-4AY0
Active

Siemens SITOP battery module, 6AG1134-0GB00-4AY0, 24 V DC, 7 Ah, 12 cells.

$417.83Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-0GB00-4AY0 key specifications
ParameterValue
Type of electrical connectionscrew-type terminals
Output voltage at DC rated value24 V
Charging current maximum2.1 A
Output current rated value40 A
Design of Short-Circuit protectionBattery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support)
For power supply unit1 screw terminal each for 0.5 ... 16 mm² for + BAT and - BAT
Depth of the enclosure110 mm
Width of the enclosure186 mm
Height of the enclosure186 mm
Wall mountingYes
Mounting height201 mm
S7 rail mountingNo
6AG1134-0GB00-4AY0 — By ambient temperature
ParameterValue
At 20 °C typical4 a
At 30 °C typical2 a
At 40 °C typical1 a
At 50 °C typical0.5 a
At 0 °C recommended28 V
At 10 °C recommended27.8 V
At 20 °C recommended27.3 V
At 30 °C recommended26.8 V
At 40 °C recommended26.6 V
At 50 °C recommended26.3 V
At -10 °C recommended28 V

All specifications

6AG1134-0GB00-4AY0 additional specifications
ParameterValue
Installation width186 mm
Standard rail mountingNo
Installation altitude at height above sea level maximum6 000 m
Ambient temperature in horizontal mounting position during operation-15 ... +50
Ambient condition relating to ambient temperature - air pressure - installation altitudeIn case of operation at altitudes of 2000 - 6000 m above sea level: Reduction of the ambient temperature by 5 K/1000 m
Ambient temperature during storageAlong with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.
Ambient temperature during storage and transport-20 ... +50
CE markingYes
Top15 mm
Left0 mm
Right0 mm
Bottom0 mm
Typicalcapacity falls to 80 % of original capacity (according to EUROBAT)
Number of cells12
Battery capacity7 A·h
Mountingcan be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Operating data noteFor storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.
Protection class IPIP20
Product component includedAccessories pack with solid-state circuitry fuse 25 A
Design of the overload protectionValve control
Operating resource protection classClass III
Display version for normal operationLED green: Battery OK; LED flashing green: Error or warning; OFF: No communication
For control circuit and status message1 screw terminal each for 0.14 ... 4 mm²
Relative temporary capacity loss at 20 °C in a month typical3 %
Product conformity of the coating qualification and performance of electrical insulating compound for printed board assemblies according to IPC-CC-830AYes; Conformal Coating, Class A

Product details

Ratings and charging parameters

The 6AG1134-0GB00-4AY0: Output current is rated 40 A; maximum charging current is 2.1 A. The 12-cell configuration uses a single screw terminal per connection, accepting 0.5 to 16 mm² wire. Capacity degradation follows EUROBAT guidelines; typical capacity falls to 80 % of original at end of design life.

Enclosure dimensions are 186 mm wide, 186 mm high, 110 mm deep. Mounting clearance requires 15 mm above the top; side and bottom clearances are 0 mm. Mounting is by wall attachment only — keyhole slots for M4 screws on a flat surface. Not compatible with S7 or standard DIN rail. Protection class is IP20. Fastening method requires screwing onto a flat surface with keyhole mounting for hooking into M4 screws.

Frequently asked questions

What are the key electrical ratings of this battery module?

24 V DC output, 7 Ah capacity, 12 cells, maximum charging current 2.1 A, output current rated 40 A.

What mounting options does this module support?

Wall mounting only via keyhole slots for M4 screws on a flat surface. It does not support S7 rail or standard DIN rail mounting.

What clearance is needed around the module for installation?

Top clearance of 15 mm is required; left, right, and bottom clearance are 0 mm.

MPN
6AG1134-0GB00-4AY0