Skip to main content
Siemens 6AG1134-4JB51-7AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-4JB51-7AB0 Analog Input, 4 ch, Pt100/Ni100,

MPN6AG1134-4JB51-7AB0

Siemens 6AG1134-4JB51-7AB0 analog input module, 4 inputs Pt100/Ni100, 24 VDC backplane power, 0.6 W, 15 x 81 x 52 mm.

$400.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-4JB51-7AB0 — Electrical
ParameterValue
Rated value (DC)24 V; From power module
Power loss (typ.)0.6 W
6AG1134-4JB51-7AB0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-25 °C; = Tmin
Temperature, max.70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-4JB51-7AB0 — Mechanical
ParameterValue
Width15 mm
Height81 mm
Depth52 mm
Weight (approx.)40 g

Product details

The Siemens 6AG1134-4JB51-7AB0 is a four-channel analog input module designed for resistance thermometers. It accepts Pt100 and Ni100 sensors in both standard and climatic ranges, and two of the four inputs support 3- or 4-wire connection to cancel lead resistance.

Conversion time per channel is 66 or 80 ms depending on the diagnostic wire-break test being active. Cycle time for all active channels equals the number of channels times the basic conversion time, up to a maximum of 8 bytes of address space. Digital filtering is parameterizable in four steps: 1x, 4x, 32x, or 64x cycle time. Integration time is selectable at 16,7 ms or 20 ms, matching 60 Hz or 50 Hz line frequencies. Diagnostics cover wire-break, overflow/underflow, and group error (SF red). Each diagnostic group can be disabled or enabled individually. The module carries CE marking. Isolation is tested at 500 V DC. Reverse polarity protection is built in. Maximum shielded cable length is 200 m.

Frequently asked questions

What is the temperature range for the 6AG1134-4JB51-7AB0?

The ambient operating and storage temperature range is -25 °C to 70 °C.

What compliance markings does this module carry?

The module bears the CE mark.

Can the input filtering be adjusted?

Yes, the module has parameterizable digital filtering in four stages: 1x, 4x, 32x, or 64x cycle time.

MPN
6AG1134-4JB51-7AB0