Siemens 6AG1134-4MB02-2AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-4MB02-2AB0 analog input module, 2-ch 4-20 mA

MPN6AG1134-4MB02-2AB0

Siemens 6AG1134-4MB02-2AB0 analog input module, 2 channels 4-20 mA, sigma-delta, short-circuit proof, -25 to 70 °C, 15 mm wide, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-4MB02-2AB0 — Electrical
ParameterValue
Rated value (DC)24 V
Power loss (typ.)1.2 W
6AG1134-4MB02-2AB0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-25 °C; = Tmin
Temperature, max.70 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-4MB02-2AB0 — Mechanical
ParameterValue
Width15 mm
Height81 mm
Depth52 mm
Weight (approx.)45 g

Product details

2-channel analog input for tight panels

The Siemens 6AG1134-4MB02-2AB0 is a 2-channel analog input module for 4-20 mA current loops, built for the ET 200SP system. It uses a sigma-delta conversion, is short-circuit proof, and supports wire-break detection on the 4-20 mA range only. Rated for -25 to 70 °C operating temperature, so it sits comfortably in warm cabinets alongside drives or transformers. The 15 mm width saves rail space when you need multiple channels. Isochronous mode is supported, and you get group diagnostics, hardware interrupt, and overflow/underflow monitoring. Max cable length is 200 m shielded.

Wiring and integration notes

Power supply is 24 V DC from the backplane bus; draws 1.2 W typical. The module expects backplane bus supply at 10 mA max. Shielded cable run up to 200 m. Wire-break detection works only on 4-20 mA range; for other ranges it must be disabled. Group diagnostics can be enabled or disabled per channel.

Frequently asked questions

What are the key ratings of this module?

2 analog inputs for 4-20 mA, sigma-delta conversion, short-circuit proof, wire-break detection on 4-20 mA only, operating temperature -25 to 70 °C, width 15 mm, depth 52 mm, height 81 mm.

Does it support isochronous mode?

Yes, isochronous mode is supported.

MPN