Skip to main content
Siemens 6AG1134-4NB51-2AB0 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-4NB51-2AB0 RTD Input Module, Pt100/Ni100, -2

MPN6AG1134-4NB51-2AB0

Siemens ET 200SP RTD input module, 2-wire, Pt100/Ni100/Pt1000/Ni1000, wire-break detection, digital filtering, -25...60 °C, 81 x 15 x 52 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-4NB51-2AB0 — Electrical
ParameterValue
Rated value (DC)24 V; From power module
Power loss (typ.)0.6 W
6AG1134-4NB51-2AB0 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Temperature, min.-25 °C; = Tmin
Temperature, max.60 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-4NB51-2AB0 — Mechanical
ParameterValue
Width15 mm
Height81 mm
Depth52 mm
Weight (approx.)40 g

Product details

The Siemens 6AG1134-4NB51-2AB0 is a current-production RTD input module for the ET 200SP distributed I/O system. It accepts Pt100, Ni100, Pt1000, Ni1000, and other common resistance thermometer types.

Key specs that matter for panel integration

Width is 15 mm — that’s one of the narrower slices in the ET 200SP family, so it packs densely on the DIN rail. Depth of 52 mm and height of 81 mm are standard for the form factor. Power draw is minimal at 0.6 W, all drawn from the 24 V DC backplane. Wire-break and group-error diagnostics are parameterizable — you can enable or disable group diagnostics and overflow/underflow reporting per module. Integration time is selectable at 16,7 ms or 20 ms, matching 50 or 60 Hz line rejection. Digital filtering stages can be set via four steps (none, low, medium, high), with corresponding cycle-time multipliers 1x, 4x, 32x, 64x. Shielded sensor cable can run up to 200 m to the field device without a repeater.

Frequently asked questions

What temperature range does it cover?

Rated for ambient operation from -25 °C to 60 °C.

What compliance documentation is available?

The module carries a CE mark. No additional certifications (such as UL or IECEx) are evidenced for this specific order code.

MPN
6AG1134-4NB51-2AB0