Skip to main content
Siemens 6AG1134-6FF00-2AA1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-6FF00-2AA1 Analog Input, 8-ch, 15/16 bit

MPN6AG1134-6FF00-2AA1
Active

Siemens ET 200SP analog input module 6AG1134-6FF00-2AA1, 8 x single-ended, 0..10 V / ±10 V, 15/16 bit resolution, 15 mm width, 24 V DC, active lifecycle.

$278.13Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-6FF00-2AA1 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)0.7 W
6AG1134-6FF00-2AA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-6FF00-2AA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)31 g

Product details

8 single-ended analog inputs, ±10 V or 0–10 V, 15/16 bit

The Siemens 6AG1134-6FF00-2AA1 is an 8-channel analog input module for the ET 200SP system, accepting 0 to +10 V with 15-bit resolution or –10 to +10 V with 16-bit including sign. Each channel is single-ended, one AI per three terminals, so watch your common reference. Input resistance sits at 100 kΩ for the 0–10 V range. Conversion time per channel is configurable: 180 ms with smoothing, down to a fast 0.625 ms (67.5 ms for the full set at 180 ms setting). Four smoothing levels (none, 4/8/16 times) are parameterizable. For applications needing noise rejection over speed, the slower settings clean up the signal. Diagnostics are built in: a group error signal, diagnostic alarm, and monitoring of the 24 V DC supply with reverse polarity protection. Each channel's status shows via a green LED; a separate green/red DIAG LED covers module health.

Panel integration – BaseUnit, space, and wiring

Width is 15 mm, depth 58 mm, height 73 mm. Mounts onto a usable BaseUnit of type A0 or A1 (sold separately). When calculating ET 200SP station fill, budget 15 mm per analog module plus the BaseUnit width. Power draw: 25 mA max current consumption from the backplane, typical power loss 0.7 W. Maximum shielded cable length is 200 m – fine for most in-cabinet or local field wiring. The module supports I&M data (I&M0 to I&M3), firmware update capability, and is parameterizable. Operating temperature range: –40 °C to +60 °C horizontally installed; can stretch to +70 °C if empty slots are configured on either side. Derating applies beyond 60 °C, but the extra thermal margin helps in crowded cabinets.

Frequently asked questions

What BaseUnit does this module require?

It is compatible with BaseUnits type A0 or A1. The module itself is 15 mm wide, so plan its slot width accordingly.

Does the module support diagnostics?

Yes, it reports a group error, supports diagnostic alarms, monitors the supply voltage, and has green channel status LEDs plus a green/red DIAG LED for module diagnostics.

MPN
6AG1134-6FF00-2AA1