Skip to main content
Siemens 6AG1134-6HB00-2CA1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-6HB00-2CA1 Analog Input, 15/16 bit, 24V

MPN6AG1134-6HB00-2CA1
Active

Siemens SIMATIC ET200SP, 6AG1134-6HB00-2CA1, analog input module, 4 AI, 15/16 bit, diagnostics, 24 V DC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-6HB00-2CA1 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)39 mA; without sensor supply
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)0.95 W; without sensor supply
Short-circuit protectionYes
6AG1134-6HB00-2CA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)60 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-6HB00-2CA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)32 g

Product details

Analog input module for ET 200SP – 4 channels, multi-range, diagnostics

The 6AG1134-6HB00-2CA1: This 4-channel analog input module fits SIMATIC ET 200SP base units type A0 or A1. Each channel can be parameterized for voltage (0 to 10 V, 1 to 5 V, ±10 V, ±5 V) or current (0 to 20 mA, 4 to 20 mA, ±20 mA) measurement. Unipolar ranges resolve to 15 bit; bipolar ranges use 16 bit including sign. Diagnostics include wire-break detection on the 4 to 20 mA range, short-circuit detection for 1 to 5 V or current ranges, two upper and two lower limit value alarms per channel, and overflow/underflow flags. A group error LED plus per-channel red LED speed fault isolation.

The resolution difference between unipolar (15 bit) and bipolar (16 bit including sign) is the same effective steps – the extra bit is the sign. Both deliver fine granularity for process signals, but the bipolar ranges give ±10 V or ±5 V with zero-center.

Dimensions 15 x 73 x 58 mm; requires base unit type A0 or A1; supply 24 V DC, power loss 0.95 W; shielded cable max 1 000 m (current) or 200 m (voltage); output current 100 mA continuous, 150 mA for < 10 s.

Frequently asked questions

What is the MSI setting for this module?

The MSI (multilingual support identifier) is set to No.

Does this module support 24 V DC supply?

Yes, the rated supply voltage is 24 V DC.

MPN
6AG1134-6HB00-2CA1