Skip to main content
Siemens 6AG1134-6HD01-2BA1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-6HD01-2BA1 Analog Input Module, 4 AI, 16-bit

MPN6AG1134-6HD01-2BA1

Siemens S7-1200 SIPLUS analog input module, 6AG1134-6HD01-2BA1, 4 differential inputs, 15/16 bit, voltage and current ranges, I&M0-3, diagnostic functions.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-6HD01-2BA1 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)0.85 W; Without encoder supply voltage
Short-circuit protectionYes
6AG1134-6HD01-2BA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Operating temperature, max. (horizontal mounting)60 °C; = Tmax
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-6HD01-2BA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)31 g

Product details

Four differential channels, clean signal path

The 6AG1134-6HD01-2BA1 is a 4-channel differential analog input module for the S7-1200 system, designed for industrial signal acquisition where noise rejection is a priority. Each channel can be configured for voltage ranges (0 to +10 V, 1 V to 5 V, -5 V to +5 V, -10 V to +10 V) or current ranges (0 to 20 mA, 4 to 20 mA), with 15-bit resolution for unipolar and 16-bit including sign for bipolar ranges. Differential inputs inherently reject common-mode noise from long cable runs, and the integrating Sigma-Delta measurement principle naturally filters line-frequency interference. Diagnostic alarms for wire-break (active on 4–20 mA) and short-circuit protection (for 1–5 V or 2-wire mode) are built in, and a group error LED provides quick visual status. I&M data (I&M0 through I&M3) is supported for device identification in the engineering tool.

Signal integrity and cabling

Isolation between channels and ground is type-tested at 707 V DC, which helps prevent ground loops in mixed-power panels. Maximum shielded cable length is 1 000 m for current signals and 200 m for voltage signals. The module mounts on BU type A0 or A1 base units, occupying a 15 mm slot in the rack.

Sourcing reality

Expect a commissioning note: power draw is 0.85 W typical without encoder supply, and the rated supply is 24 V DC.

Frequently asked questions

Does the module have wire-break detection?

Yes, wire-break detection is active when the input is configured for the 4 to 20 mA range.

What is the isolation rating between channels and ground?

Isolation is tested at 707 V DC (type test), providing common-mode rejection in noisy installations.

MPN