Skip to main content
Siemens 6AG1134-6JF00-2CA1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1134-6JF00-2CA1 AI Pt100/TC, 15 bit

MPN6AG1134-6JF00-2CA1
Active

Siemens ET 200SP, 6AG1134-6JF00-2CA1, analog input module, Pt100/TC, 16 bit incl. sign, 15 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1134-6JF00-2CA1 — Electrical
ParameterValue
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)0.75 W
6AG1134-6JF00-2CA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1134-6JF00-2CA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)32 g

Product details

This is a current-production Siemens ET 200SP analog input module — order code 6AG1134-6JF00-2CA1 — sized for RTD and thermocouple loops. It reads Pt100, Ni100, Pt1000, and most common TC types (K, J, T, E, N, R, S, B, C, L, U) with 16 bit resolution including sign, plus PTC with 15 bit. That covers the sensor range you’ll find in process and building HVAC panels.

The 15 mm width per module packs eight inputs onto a standard ET 200SP rail — useful when you’re stuffing density into a retrofitted gland plate. Wire-break detection works channel by channel, so you can flag a field cut without guessing which loop dropped. The group error output gives the CPU a single shot if any channel faults. Cable run matters on site: shielded max 200 m for resistance sensors, but only 50 m for thermocouples. That TC limit means you’ll mount the module closer to the field junction box than you might expect if you’re used to RTD runs. No oversampling onboard, so don’t count on sub-cycle acquisition — this is for stable process values, not fast dynamics.

Frequently asked questions

What is the MSI status on this module?

The MSI (Master Slave Interface) is listed as No — this module does not support MSI communication.

What is the PTC resolution?

PTC (positive temperature coefficient) sensors are supported with 15 bit resolution.

MPN
6AG1134-6JF00-2CA1