Skip to main content
Siemens 6AG1135-6HB00-2DA1 — PLCs (Programmable Logic Controllers)

Siemens 6AG1135-6HB00-2DA1 SIPLUS AQ 2xU/I High Speed, 16-bi

MPN6AG1135-6HB00-2DA1
Active

Siemens SIPLUS ET 200SP AQ 2xU/I high speed, 6AG1135-6HB00-2DA1, 2-channel analog output module, 16-bit, 0.3% accuracy, conformal coating, -40…+60 °C.

$342.90Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1135-6HB00-2DA1 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)45 mA; without load
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)0.9 W
6AG1135-6HB00-2DA1 — Environmental
ParameterValue
Installation altitude, max.5 000 m
Operating temperature, min. (horizontal mounting)-40 °C; = Tmin (incl. condensation/frost)
Operating temperature, max. (horizontal mounting)60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module
Ambient temperature vs. altitude/pressure deratingTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
6AG1135-6HB00-2DA1 — Mechanical
ParameterValue
Width15 mm
Height73 mm
Depth58 mm
Weight (approx.)31 g

Product details

The Siemens 6AG1135-6HB00-2DA1 is a SIPLUS ET 200SP analog output module, two channels of voltage or current, built for extended temperature range (-40…+60 °C) with conformal coating. It's based on the standard 6ES7135-6HB00-0DA1 but hardened for environments where condensation, vibration, or thermal swings would kill a standard card.

Output resolution hits 16-bit signed for the ±10 V and ±20 mA ranges, with fast settling: 45 µs when both channels are active, 35 µs if you only use one. That puts it in the high-speed bracket for closed-loop applications—valve control, hydraulic servo, tensioning. The power loss is only 0.9 W, which keeps the thermal load inside the ET 200SP IP20 cluster manageable. The conformal coating (not the standard module's omission) is the main decision driver. If the panel will see condensation, high humidity, or periodic washdown, this variant eliminates conformal coating as a field retrofit. The -40…+60 °C operating range covers cold storage areas and hot machine enclosures.

Frequently asked questions

What is the module's MSO status?

The MSO flag is 'No'—it is not a manufacturing stop order part.

What is the depth of this module?

The depth is 58 mm.

MPN
6AG1135-6HB00-2DA1